Group 40 — Outputs
MVX9000 User Manual 5-27
Descriptions of
Parameter Settings
Group 40 — Outputs
40.01
Analog Output Signal Range: Default: 00
00 Output Frequency (0 to Maximum Output Frequency)
01 Output Current (0 to 250% of the rated AC drive current)
02 PID Feedback Signal (0 to maximum feedback)
03 Output Power (0 to 100% of the rated AC drive power)
This parameter selects the reference value for the 0 – 10V
analog output (AO+ to COM).
40.02
Analog Output Gain Range: 0 to 200% Default: 100
Unit: 1%
This parameter may be set during operation.
The parameter sets the voltage range for analog output
terminals AO+ to COM.
The analog output voltage is directly proportional to the
selection made in 40.01.
If setting 00 is chosen, the analog output voltage on AO+ to
COM is directly proportional to the output frequency of the
AC drive. With 40.02 set at 100%, the Maximum Output
Frequency of the AC drive corresponds to +10V DC on AO.
If setting 01 is chosen, the analog output voltage is directly
proportional to the output current of the AC drive. With 40.02
set to 100%, +10V DC corresponds to 250% of AC drive rated
current.
Note: Any type of voltmeter may be used. If the meter reads
full scale at a voltage less than 10 volts, then 40.02 should be
set by the following formula:
40.02 = ((meters full scale voltage)/10) x 100%
For Example: When using the meter with full scale of 5 volts,
adjust 40.02 to 50%
40.03
Digital Output
Terminal D01
Range: 00 to 20 Default: 02