Group 30 — Inputs
MVX9000 User Manual 5-13
Descriptions of
Parameter Settings
Example 5:
In this example, the analog input or potentiometer is programmed to run a motor
in both the forward and reverse directions. A motor will be idle (0 Hz) when the
analog input or potentiometer is at the mid-point of its scale.
Figure 5-10: Forward and Reverse Programming
Defaults:
20.07=60Hz Maximum Output Frequency
30.07=100% Potentiometer Offset
30.08=1 Bias polarity
30.09=200% Potentiometer Slope
30.10=1 Potentiometer Direction
Hz
0V
10V
0
60
60
Potentiometer Scale
Max.
Output
Freq.
(20.07)
60 Hz
30 Hz
0 Hz
0V
5V
10V
30 Hz
60 Hz
REV
FWD
REV.
FWD.