EasyManua.ls Logo

Eaton MVX9000 - Figure 5-6: 0 - 10 V Analog Input

Eaton MVX9000
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Group 30 — Inputs
MVX9000 User Manual 5-9
Descriptions of
Parameter Settings
Example 1:
This example shows a standard 0 – 10V analog input (either from the keypad
potentiometer or an external source). A 0V input = 0 Hz and 10V input =
maximum output frequency.
Figure 5-6: 0 – 10V Analog Input
Defaults:
20.07=60Hz Maximum Output Frequency
30.07=0% Potentiometer Offset
30.08=0 Bias polarity
30.09=100% Potentiometer slope
30.10=0 Potentiometer direction
Hz
0V
10V
30
0
60
Potentiometer Scale
Max.
Output
Freq.
Max.
Output
Freq.
(20.07)
60 Hz
10V
20 mA
5V
12 mA
0V
4 mA
0 Hz

Table of Contents