B-14 MVX9000 User Manual
Parameter Tables
Table B-7: 80 — KEYPAD/DISPLAY (Continued)
Table B-8: 90 — COMMUNICATION PARAMETERS
Modbus Groups Page # Description Range Default
User
Settings
0609H 80.10 5-62 Parameter Lock and
Configuration
00: All parameters can be set
and read
00
01: All parameters are read
only
10: Reset all parameters to
the factory defaults
060AH 80.11 5-62 Elapsed Time (Run):
Day
0 to 65535 (show 6553.) 0
060BH 80.12 5-62 Elapsed Time (Run):
Minutes
0 to 65535 (show 6553.) 0
060CH 80.13 5-62 Elapsed Time (Power
on): Day
0 to 65535 (show 6553.) 0
060DH 80.14 5-62 Elapsed Time (Power
on): Minutes
0 to 65535 (show 6553.) 0
060EH 80.15 5-62 Automatic Display
Scroll
00: Disable
01: Scroll every 5 seconds
after 1 minute delay
02: Scroll every 15 seconds
after 1 minute delay
00
Modbus Groups Page # Description Range Default
User
Settings
0700H 90.01 5-63 Communication
Protocol
00: MODBUS ASCII mode
< 7 data bits, no parity, 2 stop
bits >
00
01: MODBUS ASCII mode
< 7 data bits, even parity,
1 stop bit >
02: MODBUS ASCII mode
< 7 data bits, odd parity,
1 stop bit >
03: MODBUS RTU mode
< 8 data bits, no parity, 2 stop
bits >
04: MODBUS RTU mode
< 8 data bits, even parity,
1 stop bit >
05: MODBUS RTU mode
< 8 data bits, odd parity,
1 stop bit >
0701H 90.02 5-63 RS-485
Communication
01 to d 254 01
0702H 90.03 5-63 Transmission Speed 00: 4800 baud 01
01: 9600 baud
02: 19200 baud
03: 38400 baud