MVX9000 Parameter Listing
MVX9000 User Manual B-15
Parameter Tables
Table B-8: 90 — COMMUNICATION PARAMETERS (Continued)
Modbus Groups Page # Description Range Default
User
Settings
0703H 90.04 5-64 Transmission Fault
Treatment
00: Display fault and continue
operating
03
01: Display fault and RAMP to
stop
02: Display fault and COAST
to stop
03: No fault displayed and
continue operating
0704H 90.05 5-64 Over time Detection 0.0: Disable 0.0
0.0~120.0 sec
0705H 90.06 5-65 Communication
frequency
reference
0.0 to 400.0 Hz 0.0
0706H 90.07 5-65 Communication
command
Bit 0-1: 00 no function
01 Stop
10 Run
11 JOG + Run
Bit 2-3: Reserved
Bit 4-5: 00 no function
01 Forward
10 Reverse
11 Change direction
Bit 6-15: Reserved
NA
0707H 90.08 5-65 Communication for
EF/RESET
Bit 0: 1 EF On
Bit 1: 1 Reset
Bit 2-15: Reserved
NA
0708H 90.09 5-65 Status monitor for
error code
00: No Fault occurred NA
01: Over-current (oc)
02: Over-voltage (ov)
03: Overheat (oH)
04: Overload (oL)
05: Overload 1 (oL1)
06: Overload 2 (oL2)
07: External Fault (EF)
08: CPU Failure 1 (CF1)
09: CPU Failure 2 (CF2)
10: CPU Failure 3 (CF3)
11: Hardware Protection
Failure (hpF)
12: Over-current During Accel
(OCA)
13: Over-current During Decel
(OCd)
14: Over-current During
Steady State (OCn)
15: Ground Fault or Fuse
Failure (GFF)
16: Reserved
17: 3-Phase Input Power Loss
18: External Pause Function
(bb)