MVX9000 Parameter Listing
MVX9000 User Manual B-5
Parameter Tables
Table B-3: 40 — OUTPUTS
Modbus Groups Page # Description Range Default
User
Settings
0200H 40.01 5-27 Analog Output Signal 00: Frequency Hz 00
01: Current A
02: Feedback signal 0 – 100
03: Output Power 0 – 100%
0201H 40.02 5-27 Analog Output Gain 00 to 200% 100
0202H
0203H
40.03
40.04
5-27
5-28
Digital Output
Terminal
(DO1-DCM)
Relay Output
Terminal
(RO1, RO2, RO3)
00: Not used 02
03
01: Ready
02: Inverter Output is active
03: Inverter Fault
04: Warning (PID feedback
loss, communication fault)
05: At speed
06: Zero speed
07: Above Desired Frequency
(40.05)
08: Below Desired Frequency
(40.05)
09: PID supervision
10: Over Voltage Warning
11: Over Heat Warning
12: Over Current Stall
Warning
13: Over Voltage Stall
Warning
14: Low voltage
15: PLC Program running
16: PLC Program Step
completed
17: PLC Program completed
18: PLC Operation paused
19: Final count value attained
20: Intermediate count value
attained
21: Reverse direction
notification
22: Under current detection
23: Inverter RUN command
state
0204H 40.05 5-30 Desired Frequency
Attained
0.0 to 400.0 Hz 0.0
0205H 40.06 5-30 Digital Output (RO4,
RO5, RO6)
same as 40.03 to 40.04 0
0206H 40.07 5-30 Digital Output (RO7,
RO8, RO9)
same as 40.03 to 40.04 0