MVX9000 Parameter Listing
B-4 MVX9000 User Manual
Parameter Tables
Table B-2: 30 — INPUTS (Continued)
Modbus Groups Page # Description Range Default
User
Settings
010BH
010CH
010DH
010EH
30.12
30.13
30.14
30.15
5-15
5-15
5-16
5-16
Digital Input Terminal
(DI3)
Digital Input Terminal
(DI4)
Digital Input Terminal
(DI5)
Digital Input Terminal
(DI6)
17: Acceleration/Deceleration
l Prohibit
05
06
07
03
18: Run Enable
19: Base Block (NO)
20: Base Block (NC)
21: PID Disable
22: Run PLC Program
23: Pause PLC Program
24: Counter Trigger signal
25: Counter Reset
26: First/second Source of
Master Frequency
27: Increase speed during
RUN or STOP state
28: Decrease speed during
RUN or STOP state
29: Output Shut Off (NO)
30: Output Shut Off (NC)
31: Auto Location – Operation
& Frequency by First source
(P50.01 & P50.02)
32: Hand Location –
Operation & Frequency by
Second source (P50.57 &
P50.60)
33: LOC – Operation &
Frequency by Second source
(P50.57 & P50.60)
010FH 30.16 5-25 Final Count Value 00 to 9999 00
0110H 30.17 5-25 Intermediate Count
Value
00 to 9999 00
0111H 30.18 5-25 1st Preset Speed 0.0 to 400.0 Hz (100.0%) 0.0
0112H 30.19 5-25 2nd Preset Speed 0.0 to 400.0 Hz (100.0%) 0.0
0113H 30.20 5-25 3rd Preset Speed 0.0 to 400.0 Hz (100.0%) 0.0
0114H 30.21 5-25 4th Preset Speed 0.0 to 400.0 Hz (100.0%) 0.0
0115H 30.22 5-26 5th Preset Speed 0.0 to 400.0 Hz (100.0%) 0.0
0116H 30.23 5-26 6th Preset Speed 0.0 to 400.0 Hz (100.0%) 0.0
0117H 30.24 5-26 7th Preset Speed 0.0 to 400.0 Hz (100.0%) 0.0
0118H 30.25 5-26 Display Hz or % 00: Frequency (Hz) 00
01: Percentage (%)
02: User Definition by 0.000 –
max. unit
0119H 30.26 5-26 Extension Input DI7 same 30.12 to 30.15 00
011AH 30.27 5-26 Extension Input DI8 same 30.12 to 30.15 00
011BH 30.28 5-26 User Definition
Display Frequency
Max Unit
0.000 – 1.000 1.000