Group 30 — Inputs
MVX9000 User Manual 5-7
Descriptions of
Parameter Settings
Group 30 — Inputs
30.01
Minimum Reference
Value (0 – 10V)
Range: 0.0 to 10.0V Default: 0.0
Unit: 0.1
This parameter sets the analog voltage input value referenced
to the Minimum Output Frequency (50.09).
30.02
Maximum Reference
Value (0 – 10V)
Range: 0.0 to 10.0V Default: 10.0
Unit: 0.1
This parameter sets the analog voltage input value referenced
to the Maximum Output Frequency (50.04).
30.03
Invert Reference Signal
(0 – 10V)
Range: Default: 00
00 Not inverted
01 Inverted
30.04
Minimum Reference
Value (4 – 20 mA)
Range: 0.0 to 20.0 mA Default: 4.0
Unit: 0.1
This parameter sets the analog current input value referenced
to the Minimum Output Frequency (50.09).
30.05
Maximum Reference
Value (4 – 20 mA)
Range: 0.0 to 20.0 mA Default: 20.0
Unit: 0.1
This parameter sets the analog current input value referenced
to the Maximum Output Frequency (50.04).
30.06
Invert Reference
Signal (4 – 20 mA)
Range: Default: 00
00 Not inverted
01 Inverted
30.07
Potentiometer Offset Range: 0.0 to 100.0% Default: 0.0%
Unit: 0.1%
This parameter may be set during operation.
This parameter provides a frequency offset for the analog input.
Example: Potentiometer Offset = (10 Hz/60 Hz) x 100.