Group 40 — Outputs
MVX9000 User Manual 5-29
Descriptions of 
Parameter Settings
Function Explanations
00 Not Used: all unused output terminals of the AC drive should be set to 00.
01 Ready: The output terminal will be active when the drive has no faults and is
ready to run.
02 Inverter Output is Active: The output terminal will be active when the drive is 
generating an output from the T1, T2, T3 terminals.
03 Inverter Fault: The output terminal will be activated when faults occur 
(oc, ov, oH, oL, oL1, EF, cF3, hpF, ocA, ocd, ocn, GF).
04 Warning: The output terminal will be active when there is a fault with 
communication or PID feedback.
05 At Speed: The output terminal will be active when the drive output
frequency reaches the value set by your command source.
06 Zero Speed: The output terminal will be active when the drives U, V, W
terminals are generating no output.
07 Above Desired Frequency: The output terminal will be active when the
output frequency is above the desired frequency (40.05).
08 Below Desired Frequency: The output terminal will be active when the
output frequency is below the desired frequency (40.05).
09 PID supervision
10 Over Voltage Warning: The output terminal will be active when output
voltage of the drive exceeds 90% of the maximum voltage limit.
11 Over Heat Warning: The output terminal will be active when temperature 
of the drive exceeds 90% of the maximum heat limit.
12 Over Current Stall Warning: The output terminal is active when the over
current stall function is enabled.
13 Over Voltage Stall Warning: The output terminal will be active when the over
voltage stall function is enabled.
14 Low Voltage: The output will be active when the input voltage drops below
the minimum voltage limit.
15 PLC Program running: The output terminal will be active when the PLC
function is running.
16 PLC Program Step complete: The output terminal will be active when each
PLC step is completed.
17 PLC Program Completed: The output terminal will be active when the PLC
function has completed and stopped. 
18 PLC Program Pause: The output terminal will be active when the PLC
function has been paused.
19 Final count value attained: The output terminal will be active when the count
reaches the setting in 30.16.
20 Intermediate count value attained: The output terminal will be active when
the count reaches the setting in 30.17.
21 Reverse direction notification: The output terminal will be active when the
drive is in reverse.
22 Under current detection: The output terminal will be active when the output
current is under 70.11 and the time has exceeded 70.13.
23 Inverter RUN state: The terminal will be active when the MVX is in a RUN 
state, the terminal will be inactive when the MVX is in a STOP state.