EasyManua.ls Logo

Eaton MVX9000 - Table 5-5: Communication Protocol

Eaton MVX9000
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Group 90 — Communications
MVX9000 User Manual 5-69
Descriptions of
Parameter Settings
Table 5-5: Communication Protocol
ASCII mode
RTU mode
STX
ADR
1
ADR
0
CMD
1
CMD
0 0 1 ...... N-1 N ETX
CHK
1
CHK
0
02H Address CMD Data characters 03H Check Sum
STX Start character: (3AH)
ADR 1 Communication address:
8-bit address consists of 2 ASCII codes
ADR 0
CMD 1
CMD 0
DATA (n-1) Contents of data:
Maximum: 20-word registers
........
DATA 0
LRC
CHK 1
LRC check sum:
8-bit check sum consists of 2 ASCII codes
LRC
CHK 0
END 1 END characters:
END 1 = CR (0DH), END 0 = LF (0AH)
END 0
START A silent interval of more than 10 ms
ADR Communication address:
8-bit address
CMD Command code:
8-bit command
DATA (n-1) Contents of data:
Maximum: 20-word registers
........
DATA 0
CRC CHK Low CRC check sum:
16-bit check sum consists of 2 8-bit characters
CRC CHK High
END A silent interval of more than 10 ms

Table of Contents