Technical Data
A-4 MVX9000 User Manual
Technical Data
Table A-2: MVX9000 230V Specifications (Continued)
Voltage Class 230V Series
Operating
Characteristics
Frequency
Setting
Keypad Set by UP, DOWN keys or potentiomenter
External
Signal
Potentiometer-5 kW/0.5W, 0 to +10V DC or 0 to +5V
(Input impedance 47 kW), RS-485 interface, 4 to 20 mA
(Input impedance 250Ω), 1 to 7 step speeds, PID feedback
Operation
Setting
Signal
Keypad Set by START, STOP, RIGHT and LEFT keys
External
Signal
FWD/STOP, REV/STOP (RUN/STOP, FWD/REV),
3-wire control, serial communication
Digital Input Signal Multi-step selections 1 to 7, Jog, acceleration/deceleration
inhibit, first/second acceleration/deceleration switch, counter,
External BB (Pause), PLC operation. Terminals have 5V
potential and must be brought to DC common to enable
(Sinking).
Digital Output Indication Operating, Up to frequency, Desired frequency,
Non-zero B.B., Abnormal indication, Local/Remote indication,
PLC, Low Voltage.
Analog Output Signal Analog frequency/current signal output.
Other Functions AVR, S-Curve, Over-Voltage, Over-Current stall prevention,
Fault records checking, Carrier Frequency adjustable,
DC injection braking, Momentary power loss restart,
Frequency limit setting, Parameter lock/reset,
Frequency input operation method selection,
Reverse run inhibit, etc.
Protection Self-testing, Over-voltage, Over-current,
Under-voltage, Overload, Overheating, External Fault,
Ground Fault, I
2
t.
Cooling Systems Forced air-cooling
Environment Installation Location Altitude 1,000m or lower, keep from corrosive gasses,
liquid and dust
Pollution Degree 2
Ambient Temperature -10 to 50 (Non-Condensing and not frozen)-10 to 40°C for
the models of 5.5 kW and higher
Storage Temperature -20 to 60
Ambient Humidity Below 90% RH (non-condensing)
Vibration 9.80665 m/s
2
(1G) less than 20 Hz, 5.88 m/s
2
(0.6G)
at 20 to 50 Hz