Group 30 — Inputs
MVX9000 User Manual 5-25
Descriptions of
Parameter Settings
30.16
Final Count Value Range: 00 to 9999 Default: 00
This parameter defines the final count value for the MVX9000
internal counter. The counter is incremented by a low-to-high
transition on a Digital Input Terminal: DI3 to DI6.
A selected Digital/Relay Output Terminal may be
programmed to activate upon completion of the final count.
30.17
Intermediate Count
Value
Range: 00 to 9999 Default: 00
This parameter sets the intermediate count value for the
MVX9000 internal counter. The counter is incremented by a
low-to-high transition on a Digital Input Terminal: DI3 to DI6.
The count will start at c01.
A selected Digital/Relay Output Terminal may be
programmed to activate upon completion of the intermediate
count.
30.18
Preset Speed 1 Range: 0.0 to 400.0 Hz Default: 0.0 Hz
Unit: 0.1 Hz
30.19
Preset Speed 2 Range: 0.0 to 400.0 Hz Default: 0.0 Hz
Unit: 0.1 Hz
30.20
Preset Speed 3 Range: 0.0 to 400.0 Hz Default: 0.0 Hz
Unit: 0.1 Hz
30.21
Preset Speed 4 Range: 0.0 to 400.0 Hz Default: 0.0 Hz
Unit: 0.1 Hz