below 50% of the full rotaonal speed. Refer to Table: Operang and storage condions
on page 20 for pump operang ranges. Refer to Cooling on page 55 for advice on pump
cooling.
6.8.3 Protecon against over-speed
Control soware in the motor controller controls the pump rotaonal speed and
prevents the operaon of the pump more than its normal full rotaonal speed.
If the control soware fails, the motor controller has a built‑in safety circuit that checks
if the pump is operang at over‑speed. If an over‑speed condion is detected, the motor
controller automacally stops the power to the pump motor and slows the pump to a
stop. The motor controller signals a fail condion if over‑speed is detected.
If the pump is operang at over‑speed, set the pump to o and contact us or the
supplier.
6.8.4 Electrical supply failure
WARNING: POWER SUPPLY FAILURE
Risk of injury. If the power supply fails when the pump is in operaon, the rotor can
spin for approximately 30 minutes. The control circuit can possibly not give indicaon
that the rotor is spinning.
WARNING: AUTOMATIC RESTART
Risk of injury. If the parallel start control signal on the logic interface connector is set
to start, the pump can automacally restart when the electrical supply is restored
aer an electrical supply failure. Make sure that people do not get injured by the
rotang blades of the pump.
If the electrical supply to the pump fails when the pump is in operaon, the motor of the
pump is used as a generator.
The regenerated power is used to:
▪
keep the output signals on the logic interface (such as the normal signal and serial
communicaons)
▪
power the indicator LEDs on the motor controller
▪
keep the power at the motor controller auxiliary outputs (to control the vent valve
or fan, if installed).
When the electronic braking is enabled, the regenerated power is available at the power
supply pins of the logic interface connector (refer to Electronic braking on page 14). This
can be used to power other instruments through short power interrupons. The
minimum voltage of this supply will be 24 V d.c.-20% (19.2 V) provided that the external
load is not excessive and it can be sustained at that minimum voltage when operang
from supply voltages above 48 V d.c. -20% and below 48 V d.c. +5%.
As the rotaonal speed of the pump decreases, the power generated from the motor
also decreases unl it is no longer able to keep power to the logic interface or LEDs. This
will occur at speeds less than 50% full rotaonal speed. There will be no indicaon of
pump rotaonal speed, but the rotor can possibly connue to operate.
Page 79
B8G000880_D - Operaon