Emotron VSB Instruction Manual Chapter 6 Specification of Parameters
C1-15
Zero current detection
Range: 0.0% - 50.0%
Factory default:
C1-16 Zero current detection time
Range: 0.01s - 50.00s
Factory default:
The two parameters should be set with digital output terminal "zero current detection". When
the drive output current is less than C1-15 and its lasting time attains the value of C1-16,
terminal "zero current detection" outputs ON signal. See Fig. 6-16:
Fig. 6-16
Group C2 Analogue and Pulse Input
Curves of analogue input AI is selected by this parameter.
Unit's place: AI input curve
0: Curve 1 (2 points)
Defined by C2-01 - C2-04.
1: Curve 2 (4 points)
Defined by C2-05 - C2-12.
Decade: Potentiometer input curve
Same as AI above.
时间
输出电流
时间
零电流检测端子
零电流检出水平
零电流检出
时间
运行
停机
Zero current detection level
Zero current detection terminal
current
- 102 -