Emotron VSB Instruction Manual Chapter 6 Specification of Parameters
E1-11 Relay action on drive fault Range: 000 - 111
Factory default:
010
Unit's place: when undervoltage fault occurs
0: No action
1: Action enabled
Set whether or not fault relay acts when undervoltage occurs.
Decade: when fault locked
0: No action
1: Action enabled
Set whether or not the relay acts when the fault locked at latest power loss after power up.
Hundred's place: time of automatic reset
0: No action
1: Action enabled
Set whether or not the relay is to operate when fault occurs in automatic reset status.
E1-13
Drive thermal alarm
threshold
Range: 0.0 °C - 100.0 °C
Factory default:
80.0 °C
Sets the threshold of drive thermal alarm. When the maximum internal temperature of drive is
higher than this value, the drive displays thermal alarm code "oH1", but won’t influence the
running.