Emotron VSB Instruction Manual Chapter 7 Troubleshooting
Fault
code
Fault
Display
Fault description Causes Solutions
current is too big
12 GdP
Output ground
short-circuit
protection
Output connection
ground short circuit
Check motor connection
and output ground
impedance
Motor insulation
abnormal
Check the motor
Inverter module
abnormal
Seek services
Output ground leakage
current is too big
Seek services
13 ISF
Input power
supply abnormal
Serious voltage
imbalance among three
phases of power supply
Check power grid
voltage
Abnormal bus
capacitance
Seek services
Abnormal input wiring of
power supply
Check power supply
input wiring
14 oPL
Output phase
loss
Motor cable connection
abnormal
Check motor connection
Imbalance among motor
three phases
Check or replace the
motor
Incorrect setting of vector
control parameters
Correctly set vector
control parameters
16 oH1
Heat sink
thermal
protection
Ambient temperature is
too high
Drop ambient
temperature
Fan damaged
Replace the fan
Air duct blocked
Clear air duct
Temperature sensor
abnormal
Seek services
Inverter module
abnormal
Seek services
18 oH3
Module
temperature
detection
undisconnected
Module detection circuit
damaged
Seek services
Thermistor damaged Seek services
Ambient temperature is
Raise ambient
- 152 -