EasyManuals Logo

Emotron VSB Series User Manual

Emotron VSB Series
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #89 background imageLoading...
Page #89 background image
Emotron VSB Instruction Manual Chapter 6 Specification of Parameters
ATTENTION:
Output frequency of drive can normally pass through skip zones during Accel and Decel.
b0-19 Jog frequency
Range: 0.00Hz - upper limit
frequency
Factory default:
5.00Hz
This parameter sets the running frequency during jog. Jog Accel time is set by parameter b2-10
while its Decel time by parameter b2-11.
Jog run command control could be performed through keypad, control terminals or
communication input.
Multifunction MF key can be set as forward jog or reverse jog key through parameter
L0-00.
Jog can be realized using "forward jog terminal” and "reverse jog terminal” of DI.
Jog can be realized via communication input. See drive communication protocol for further
information.
See Jog diagrammatic sketch 6-8.
Fig. 6-8
Thereof:
f1 is jog frequency b0-19
t1 represents the ACC time from zero to jog frequency; t1 = (b2-10) × f1/(b0-08); b0-08 is
the maximum frequency.
t2 is the DEC time from jog frequency to 0; t2 = (b2-11) × f1/(b0-08).
ATTENTION:
Set value of jog frequency is free from limitations of upper and lower limit frequency.
Jog is started from starting frequency and its start is not subject to limitation by b1-05.
f
1
运行频率
时间
t1
t2
Running frequency
Time
- 83 -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emotron VSB Series and is the answer not in the manual?

Emotron VSB Series Specifications

General IconGeneral
BrandEmotron
ModelVSB Series
CategoryController
LanguageEnglish

Related product manuals