Emotron VSB Instruction Manual Chapter 5 List of Parameters
Param
Designation Range
Factory
default
Attr
U0-11
Drive
status
Unit's place: run status
0: Accelerating
1: Decelerating
2: Constant speed running
Decade: drive status
0: Stop
1: Run status
2: Autotuning
00
U0-12
AI input voltage
0.00V~10.00V
0.00V
U0-13
Potentiometer input voltage
0.00V~10.00V
0.00V
U0-15
AO output
0.0%~100.0%
0.0%
U0-18
Status of digital input terminal
0~F
0
U0-19
Status of digital output terminal
0~5
0
U0-20
PID set
0.0%~100.0%
0.0%
U0-21
PID feedback
0.0%~100.0%
0.0%
U0-22
PID input offset
-100.0%~100.0%
0.0%
U0-30
Cumulative power-up time
0h~65535h
0h
U0-31
Cumulative run time
0h~65535h
0h
U0-33
IGBT temperature
-40.0 °C ~100.0 °C
0.0 °C
U0-36
Run command record at LoU
0~1
0
U0-37
Fault code record at LoU
0~100
0
U0-39
Curr
ent detection fault source
0: No fault source
1: IU
2: IV
3: IW
0
U0-42
Higher of keypad
/
stored
value
0,- 0
U0-43
Lower of keypad / stored
value
-999.9Hz600.0Hz 0.00Hz
U0-44
Higher of terminal UP/DOWN stored
value
0,- 0
U0-45
Lower of terminal UP/DOWN
stored value
-999.9Hz600.0Hz 0.00Hz
Group U1 Fault History
U1-00
Fault 1 code(latest)
0: No fault
1: Accel overcurrent
2: Constant-
speed overcurrent
3: Decel overcurrent
4: Accel overvoltage
5: Constant-speed overvoltage
0
- 67 -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emotron VSB Series and is the answer not in the manual?

Emotron VSB Series Specifications

General IconGeneral
BrandEmotron
ModelVSB Series
CategoryController
LanguageEnglish

Related product manuals