Emotron VSB Instruction Manual Chapter 6 Specification of Parameters
E1-04 Overload alarm threshold Range: 20.0% - 200.0%
Factory default:
130.0%
When 0 is set at decade of E1-03, this set value is a percentage compared to rated current of
motor. When 1 is set of that, this set value is a percentage compared to rated current of drive.
E1-05
Overload alarm activated
time
Range: 0.1s - 60.0s
Factory default:
5.0s
Sets the lasting time that overload alarm is activated when output current of drive is bigger than
the threshold set by E1-04.
E1-06 Protection action 1 Range: 0000 - 1010
Factory default:
0000
E1-07 Protection action 2 Range: 0000 - 1010
Factory default:
0000
These two parameters set the drive protection action in the following abnormal status.
Specification of E1-06:
Unit's place: reserved
Decade: temperature sampling disconnection action
0: Protection enabled and coast to stop
1: Continue to run
Hundreds place: reversed
Thousands place: abnormal terminal communication
0: Protection enabled and coast to stop
1: Continue to run
Specification of E1- 07:
Unit's place: reserved
Decade: current detection circuit failed
0: Protection enabled and coast to stop
1: Continue to run
Hundreds place: reversed
Thousands place: output phase loss
0: Protection enabled and coast to stop
1: Continue to run
- 128 -