Emotron VSB Instruction Manual Chapter 5 List of Parameters
Param
Designation Range
Attr
2: Seven-segment mode
Hundreds place: over-modulation
adjustment
0: Disabled
E0-02
un time attained
Unit's place: selection when
consecutive running time attained:
0: Continue to run
1: Stop and fault alarm
Decade: selection when
accumulative run time attained:
0: Continue to run
1: Stop and fault alarm
Hundreds place: unit of run time
0: Second
000 ×
Consecutive run time setting
Accumulative running time setting
Group E1 Protection Parameters
E1-00
1 ×
E1-01
Overvoltage stall protection voltage
200V: 100%~120% default: 116%
400V: 120%~150% default: 135%
Model
×
E1-02
0 ×
E1-03
prealarm
Unit's place: detection option:
0: Always detect
1: Detect at constant speed only
Decade: compared object:
0: Motor rated current
1: Drive rated current
Hundreds place: alarm option
0: Continue to run
1: Protection enabled and coast to
000 ×
Overload prealarm threshold
△
Overload prealarm detected time
△
E1-06
ed action 1
Decade: temperature sampling
disconnection action:
0: Protection enabled and coast
0000 ×
- 60 -