Cerabar M PMC51, PMP51, PMP55
16 Endress+Hauser
Damping
A damping affects all outputs (output signal, display):
• Via on-site display, handheld terminal or PC with operating program, continuous from 0...999 s
• Via DIP-switch on the electronic insert, switch position
"on" (= set value) and "off" (= damping switched off)
• Factory setting: 2 s
Firmware version
Designation Option
1)
01.00.zz, FF, DevRev01 76
01.00.zz, PROFIBUS PA, DevRev01 77
01.00.zz, HART, DevRev01 78
1) Product Configurator, "Firmware version" ordering feature
Protocol-specific data HART
Manufacturer ID 17 (11 hex)
Device Type Code 25 (19 hex)
Device Revision 01 (01 hex) - SW version 01.00.zz
HART specification 6
DD Revision • 01 (Dutch))
• 02 (Russian))
Device description files (DTM, DD) Information and files can be found:
• www.endress.com
• www.fieldcommgroup.org
HART load Min. 250 Ω
HART device variables The measured values can be freely assigned to the device variables:
Measured values for PV (primary variable)
• Pressure
• Level
• Tank content
Measured values for SV, TV (second and third variable)
• Pressure
• Level
Measured values for QV (fourth variable)
Temperature
Supported functions • Burst mode
• Additional Transmitter Status
• Device Locking
• Alternative operating modes
Wireless HART data
Minimum starting voltage 11.5 V
1)
Start-up current 12 mA (default) or 22 mA (customer setting)
Starting time 5 s
Minimum operating voltage 11.5 V
1)
Multidrop current 4 mA
Time for connection setup 1 s
1) Or higher if operating near ambient temperature limits (–40 to +85 °C (–40 to +185))
Protocol-specific data
PROFIBUS PA
Manufacturer ID 17 (11 hex)
Ident number 1554 hex
Profile Version 3.02
SW Version 01.00.zz
GSD Revision 5