Cerabar M PMC51, PMP51, PMP55
6 Endress+Hauser
Terms and abbreviations
URL OPLMWP
LRL
0
p
LRV
URV
1
2
3
4
A0029505
Item Term/abbreviation Explanation
1 OPL The OPL (over pressure limit = sensor overload limit) for the measuring device depends on the lowest-rated element,
with regard to pressure, of the selected components, i.e. the process connection has to be taken into consideration in
addition to the measuring cell. Also observe pressure-temperature dependency. For the relevant standards and
additional notes see the →  47 section.
The OPL may only be applied for a limited period of time.
2 MWP The MWP (maximum working pressure) for the sensors depends on the lowest-rated element, with regard to
pressure, of the selected components, i.e. the process connection has to be taken into consideration in addition to the
measuring cell. Also observe pressure-temperature dependency. For the relevant standards and additional notes see
the →  47 section.
The MWP may be applied at the device for an unlimited period.
The MWP can also be found on the nameplate.
3 Maximum sensor
measuring range
Span between LRL and URL
This sensor measuring range is equivalent to the maximum calibratable/adjustable span.
4 Calibrated/adjusted
span
Span between LRV and URV
Factory setting: 0 to URL
Other calibrated spans can be ordered as customized spans.
p - Pressure
- LRL Lower range limit
- URL Upper range limit
- LRV Lower range value
- URV Upper range value
- TD (Turn down) Turn down
Example - see the following section.