Cerabar M PMC51, PMP51, PMP55
8 Endress+Hauser
Function and system design
Device selection
A0023673
PMC51 with capacitive measuring cell and ceramic process isolating diaphragm (Ceraphire®)
A0023675
PMP51 with piezoresistive measuring cell and metal welded process isolating diaphragm
A0023676
PMP55 with diaphragm seal
Field of application
Gauge pressure and absolute pressure
Level
Process connections
PMC51:
Thread
EN flanges DN 25 – DN 80
ANSI flanges 1" – 4"
JIS flanges 50 A – 100 A
Flush mount hygienic connections
PMP51:
Thread
EN flanges DN 25 – DN 80
ANSI flanges 1" – 4"
Prepared for diaphragm seal mount
Flush mount hygienic connections
PMP55:
Wide range of diaphragm seals
Measuring ranges
PMC51: From –100/0 to 100 mbar (–1.5/0 to 1.5 psi) to –1/0 to 40 bar (–15/0 to 600 psi)
PMP51: From –400/0 to 400 mbar (–6/0 to 6 psi) to –1/0 to 400 bar (–15/0 to 6000 psi)
PMP55: From –400/0 to 400 mbar (–6/0 to 6 psi) to –1/0 to 400 bar (–15/0 to 6000 psi)