Cerabar M PMC51, PMP51, PMP55
Endress+Hauser 31
Installation factors Influence of installation position
A0023697
Measuring error in mbar (psi)
Process isolating diaphragm axis is
horizontal (A)
Process isolating diaphragm
pointing upwards (B)
Process isolating diaphragm
pointing downwards (C)
Calibration position, no measuring error < +0.2 mbar (+0.003 psi) < –0.2 mbar (–0.003 psi)
A position-dependent zero point shift can be corrected on the device.
Warm-up period
• 4 to 20 mA analog: ≤1.5 s
• 4 to 20 mA HART: ≤5 s
• PROFIBUS PA: ≤8 s
• FOUNDATION Fieldbus: ≤20 s (after a TOTAL reset ≤45 s)