Cerabar M PMC51, PMP51, PMP55
28 Endress+Hauser
Total error
The total error of the measuring device comprises the total performance and the influence of long-
term stability and is calculated using the following formula:
Total error = total performance + long-term stability
Calculation of the total error with the Endress+Hauser Applicator
Detailed measured errors, such as for other temperature ranges, for example, can be calculated with
the Applicator "Sizing Pressure Performance".
A0038927
Calculation of the diaphragm seal error with the Endress+Hauser Applicator
Diaphragm seal errors are not taken into consideration. Diaphragm seal errors are calculated
separately in the Applicator "Sizing Diaphragm Seal".
A0038925
Long-term stability
The specifications refer to the upper range limit (URL).
400 mbar (6 psi) and 1 bar (15 psi) sensor
• 1 year: ±0.20 %
• 5 years: ±0.40 %
• 10 years: ±0.50 %
2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi) and 40 bar (600 psi) sensor
• 1 year: ±0.10 %
• 5 years: ±0.25 %
• 10 years: ±0.40 %
With hygienic process connections
400 mbar (6 psi) and 1 bar (15 psi) sensor
• 1 year: ±0.35 %
• 5 years: ±0.50 %
• 10 years: ±0.60 %
2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi) and 40 bar (600 psi) sensor
• 1 year: ±0.20 %
• 5 years: ±0.35 %
• 10 years: ±0.50 %