System integration Proline Promag W 400 EtherNet/IP
74 Endress+Hauser
Name Description (format) Byte Bit Value
8. Not used 8 –
9. Not used 2 to 4 0 to 8 –
10. Control totalizer 1 (integer) 5 to 6 0 to 8 • 32226: Add
• 32490: Reset and stop
• 32228: Default value and stop
• 198: Reset and add
• 199: Default value and add
11. Not used 7 to 8 0 to 8 –
12. Control totalizer 2 (integer) 9…10 0 to 8 See totalizer 1
13. Not used 11 to
12
0 to 8 –
14. Control totalizer 3 (integer) 13 to
14
0 to 8 See totalizer 1
15. Not used 15 to
16
0 to 8 –
16. External pressure (real) 17 to
20
0 to 8 Data format:
Byte 1 to 4: External pressure
Floating-point number
(IEEE754)
17. External pressure unit (integer) 21 to
22
0 to 8 • 2165: Pa a
• 2116: kPa a
• 2137: MPa a
• 4871: bar a
• 2166: Pa g
• 2117: kPa a
• 2138: MPa a
• 2053: bar g
• 2182: Psi a
• 2183: Psi g
• 2244: Customer-specific
18. Not used 23 to
24
0 to 8 –
19. External reference density (real) 25 to
28
0 to 8 Data format:
Byte 1 to 4: External ref. density
Floating-point number
(IEEE754)
20. External reference density unit
(integer)
29 to
30
0 to 8 • 2112: kg/Nm
3
• 2113: kg/Nl
• 2092: g/Scm
3
• 2114: kg/Scm
3
• 2181: lb/Sft
3
21. Not used 31 to
32
0 to 8 –
22. External temperature (real) 33 to
36
0 to 8 Data format:
Byte 1 to 4: External
temperature
Floating-point number
(IEEE754)
23. External temperature unit
(integer)
37 to
38
0 to 8 • 4608: °C
• 4609: °F
• 4610: K
• 4611: °R
24. Not used 39 to
40
0 to 8 –
25. Start verification (integer) 41 to
42
0 to 8 • 32378: Start
• 32713: Cancel
26. Not used 43 to
64
0 to 8 –