Dust Mitigation and Prevention
Enterasys S-Series Stand Alone (SSA) Hardware Installation Guide E-5
Figure E-5 below shows another mitigation strategy for open racks containing sub-systems with 
mixed flow direction. Mitigation of potential hot air recirculation is achieved by separating unlike 
systems with products having front to back airflow patterns. 
Figure E-5  Another Mitigated Non-ideal Open Rack Configuration
Dust Mitigation and Prevention
Dust accumulation on inlet and exit venting is not uncommon after prolonged use. In dustier 
environments this accumulation can be much quicker. 
Enterasys strongly recommends routine maintenance to check for clean inlet and exit vents on this 
equipment. Over time, dust accumulation can create vent blockages, thereby decreasing airflow 
and increasing component temperatures, resulting in reduced reliability. Recommended 
maintenance should start with monthly inspections and be adjusted based on dust accumulation 
levels. 
Table E-1 on page E-6 notes the maximum dust and debris accumulation limits for room 
environments as a reference.