EasyManua.ls Logo

FieldServer LonWorks ProtoNode - Viewing Diagnostic Information; Checking Wiring and Settings

FieldServer LonWorks ProtoNode
97 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 42 of 97 PN: 106417-05
8.2 Viewing Diagnostic Information
Type the IP Address of the FieldServer into the web browser or use the FieldServer
Toolbox to connect to the FieldServer.
Click on Diagnostics and Debugging Button, then click on view, and then on connections.
If there are any errors showing on the Connection page, refer to Section 8.3 Checking Wiring
and Settings for the relevant wiring and settings.
Figure 8-3: Connections Page
8.3 Checking Wiring and Settings
No COMS on the Modbus RTU side. If the Tx/Rx LEDs are not flashing rapidly then there is a
COM issue. To fix this problem, check the following:
Visual observations of LEDs on the ProtoNode. Both Tx and Rx LEDs should be flashing rapidly.
Check baud rate, parity, data bits, stop bits.
Check device address.
Verify wiring.
Verify the device was listed in the Web Configurator (Section 6.3 Configure Devices Connected to the
Gateway).
Field COM problems:
Visual observations of LEDs on the ProtoNode. (Section 8.4 LED Functions)

Table of Contents

Related product manuals