EasyManua.ls Logo

FieldServer LonWorks ProtoNode - Siemens LMV36; Precision Digital Trident PD765

FieldServer LonWorks ProtoNode
97 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 68 of 97 PN: 106417-05
12.8 Siemens LMV36
Table 12-9: Siemens LMV36 LonWorks Points List
Point Name
Lon Name
Lon SNVT
Com Status
nvoComStatus_XXX
SNVT_switch
Flame Signal
nvoFlameSig_XXX
SNVT_lev_percent
Lockout Error Code
nvoLckotErCd_XXX
SNVT_count_f
Lockout Diagnostic Code
nvoLckotDgCd_XXX
SNVT_count_f
Control Mode
nvi/nvoCtrlMode_XXX
SNVT_switch
Operating Mode
nvi/nvoOp_Mode_XXX
SNVT_count_f
Fuel Rate
nvi/nvoFuelRate_XXX
SNVT_count_f
Fuel Selected
nvoFuelSel_XXX
SNVT_count_f
Firing Rate
nvoFirRate_XXX
SNVT_count_f
12.9 Precision Digital Trident PD765
Table 12-10: Precision Digital Trident PD765 LonWorks Points List
Point Name
Lon Name
Lon SNVT
Com Status
nvoComStatus_XXX
SNVT_switch
Display Value
nvoDispVal_XXX
SNVT_count_f
Relay 1 Status
nvi/nvoRel1Stat_XXX
SNVT_switch
Relay 2 Status
nvi/nvoRel2Stat_XXX
SNVT_switch
Alarm 1 Status
nvoAlm1Stat_XXX
SNVT_switch
Alarm 2 Status
nvoAlm2Stat_XXX
SNVT_switch
Alarm 1 Acknowledge
nvi/nvoAlm1Ack_XXX
SNVT_switch
Alarm 2 Acknowledge
nvi/nvoAlm2Ack_XXX
SNVT_switch
Relay 1 Set Point
nvi/nvoRl1SP_XXX
SNVT_count_f
Relay 1 Reset Point
nvi/nvoRl1ResPt_XXX
SNVT_count_f
Relay 1 Turn-on Delay
nvi/nvoRl1TnOnDl_XXX
SNVT_count_f
Relay 1 Turn-off Delay
nvi/nvoRl1TnOfDl_XXX
SNVT_count_f
Relay 1 Normal/Fail-Safe
nvi/nvoRl1NrFlSf_XXX
SNVT_switch
Relay 1 Operation
nvi/nvoRl1Oper_XXX
SNVT_count_f
Relay 2 Set Point
nvi/nvoRl2SP_XXX
SNVT_count_f
Relay 2 Reset Point
nvi/nvoRl2ResPt_XXX
SNVT_count_f
Relay 2 Turn-on Delay
nvi/nvoRl2TnOnDl_XXX
SNVT_count_f
Relay 2 Turn-off Delay
nvi/nvoRl2TnOfDl_XXX
SNVT_count_f
Relay 2 Normal/Fail-Safe
nvi/nvoRl2NrFlSf_XXX
SNVT_switch
Relay 2 Operation
nvi/nvoRl2Oper_XXX
SNVT_count_f
4-20mA Out-Mode Output Option
nvi/nvo420MdOtOp_XXX
SNVT_switch
4-20mA Out-Mode Data Source
nvi/nvo420MdDtSr_XXX
SNVT_count_f
4-20mA OutSensor Break Value
nvi/nvo420SnBkVl_XXX
SNVT_count_f
4-20mA OutOverrange value
nvi/nvo420OvrVal_XXX
SNVT_count_f
4-20mA OutUnderrange value
nvi/nvo420UndVal_XXX
SNVT_count_f
4-20mA OutMax value Allowed
nvi/nvo420MxVlAl_XXX
SNVT_count_f
4-20mA OutMin value Allowed
nvi/nvo420MnVlAl_XXX
SNVT_count_f
4-20mA OutDisplay Value 1
nvi/nvo420DspVl1_XXX
SNVT_count_f
4-20mA OutDisplay Value 2
nvi/nvo420DspVl2_XXX
SNVT_count_f
4-20mA OutOutput 1
nvi/nvo420Outpt1_XXX
SNVT_count_f

Table of Contents