Page 63 of 97 PN: 106417-05
System Pum Cycle
Count
0-999,999 (U32)
400,132-
400,133
nvi/nvoSysPmCyCt_XXX
SNVT_count_f
DHW Pump Cycle
Count
0-999,999 (U32)
400,134-
400,135
nvi/nvoDHWPmCyCt_XXX
SNVT_count_f
Boiler Pump Cycle
Count
0-999,999 (U32)
400,138-
400,139
nvi/nvoBlrPmCyCt_XXX
SNVT_count_f
CH Modbus Stat
CH Modbus STAT
0 = no demand
1 = demand
When this register is not written
every “Modbus Command Time
Out” parameter seconds (default
30 seconds), CH Modbus Stat is
reverted to 0, no demand.
400,577
nvi/nvoCHModStat_XXX
SNVT_switch
LLCH Modbus Stat
LL CH Modbus STAT
0 = no demand
1 = demand
When this register is not written
every “Modbus Command Time
Out” parameter seconds (default
30 seconds), CH Modbus Stat is
reverted to 0, no demand.
400,563
nvi/nvoLLCHModSt_XXX
SNVT_switch
CH Modbus SP
Use this register to change the
boiler setpoint.
When this register is not written
every “Modbus Command Time
Out” parameter seconds (default
30 seconds), setpoint reverts to
local setpoint. valid range 60 F to
190 F
410,579
nvi/nvoCHModSP_XXX
SNVT_temp_p
CH Sequencer
Modbus SP
Use this register to change the
multiple boiler Sequencer
setpoint.
When this register is not written
every “Modbus Command Time
Out” parameter seconds (default
30 seconds), setpoint reverts to
local setpoint. valid range 60 F to
190 F
410,562
nvi/nvoCHSeqMdSP_XXX
SNVT_temp_p
Outdoor Temperature
Building Automation may send the
controller the outdoor air
temperature. Use this register to
change the outdoor temperature.
When this register is not written
every “Modbus Command Time
Out” parameter seconds (default
30 seconds), temperature is set to
bad data quality and outdoor air
reset is set back to local setpoint.
valid range -40 F to 302 F
410,817
nvi/nvoOutTemp_XXX
SNVT_temp_p
CH Modbus Rate
Use this register to drive individual
boiler firing rates. This register is
used when firing rate control is
performed by an external Energy
Management System. Firing rate
reverts to local control when
register is not written every
“Modbus Command Time Out”
parameter seconds (default 30
seconds), Range is 0 to 200 %
provides 0-100% firing rate.
400,581
nvi/nvoCHModRate_XXX
SNVT_lev_percent
Fan Speed Measured
Speed of the combustion air
blower in rpm
400,008
nvoFanSpdMes_XXX
SNVT_count_f
Modbus command
timeout
This parameter sets the amount of
time the control will wait for input
400,763
nvoModCmdTim_XXX
SNVT_count_f