EasyManua.ls Logo

Fimer PVS-175-TL - Installation and Maintenance Safety

Fimer PVS-175-TL
185 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FIMER_PVS-175-TL A.1 Version_Product manual_EN_RevC-
F
12
Installation and maintenance safety
General safety information
WARNING – B Do not do work on the photovoltaic generator, on the inverter, on its input
or output cables, when the inverter is connected to an electrical power system, or to the
photovoltaic generator.
Before perform any maintenance operation on the inverter, follow this steps:
- Prepare the work: Carry out an on-site Risk Assessment or Job Hazard Analysis (Check
for proper tools and PPE for the job; Engage the person responsible for electrical equipment
or system to review single-line, schematics, switching plans; Define the appropriate work
methods and initiate the permit to work process).
- Clearly identify the work location and equipments.
- Disconnect all sources and secure against reconnection by means of the “Lockout/
Tagout” procedure to ensure that any conductor cannot accidentally become live.
- Verify the absence of operating voltage (This must be carried out by means of a proper
test instrument).
- Complete the permit to work and “Walk the Permit.
WARNING – B Refer to “Inverter total de-energization and safe access” paragraph on
this manual to know all detailed necessary steps to safely operate on the inverter.
WARNING – B Do not proceed with installation if the integrity of the equipment is compromised.
Do not use the equipment if you find any operating anomalies.
FORBIDDEN – H Avoid temporary repairs. All repairs should be carried out using only genuine
spare parts, which must be installed in accordance with their intended use.
FORBIDDEN – H The labels affixed on the equipment must strictly NOT be removed, damaged,
defaced, hidden, etc. The technical data provided in this manual does not in any case replace
that shown on the labels affixed on the equipment.
Environmental conditions and risks
ATTENTION – A This device can be installed outdoors, but only in environmental conditions
that do not prevent its regular operation. These conditions are listed in the technical data
and in the installation chapter.
ATTENTION – A Do not open the front covers of the inverter when it is raining, or when
sand or dust can blow into the unit. Infiltration of water or sand into the inverter can cause
damage of the unit. It is of paramount importance to evaluate the weather conditions in the
risk assessment prior any intervention on the equipment. Any intervention on the inverter
can be carried out only in case of dry environment. Don’t proceed in case of rain (even light)
or high humidity.
ATTENTION – A This device is not designed to operate in environments that are particularly
inflammable or explosive.
ATTENTION – A In the event of fire, use CO2 extinguishers and auto-extraction systems to
extinguish the fire in closed environments.
ATTENTION – A The installer or maintenance technician must always pay attention to the
work environment, ensuring that it is well-lit and there are enough escape routes.