FIMER_PVS-175-TL A.1 Version_Product manual_EN_RevC-
F
56
50cm / 20”
*100cm / 40”
(*): recommended
minimum free
space to operate
with the inverter
Do not install any object (e.g. AC or DC cables) that could be damaged by overheating from
outgoing hot air flow coming from top and side fan sections (ΔT= +15 °C compared to ambient
temperature). In case of this kind of installation needs, please evaluate the installation of a
proper air deflector. Always respect the minimum distances required.
A
C
B
C
PVS-175
The minimum clearance distances depends from multiple factor:
1. Ventilation flow coming from the top side of the inverter.
The upper (A) minimum required free space must be 25cm.
25
cm
25
cm
2. Possible flooding or damage during grass cutting operation.
If the inverter is installed in a place where there are risks of flooding or it is needed to cut the grass
growing underneath the unit, the bottom (B) minimum recommended free space is 50 cm; otherwise
the required free space can be reduced to 15 cm.