Maintenance Instructions
18.12.15 Kapitel/Chapter 7: Maintenance Instructions - Seite/Page 171
7.21 Checking the Flame Glow Plug (optional unit)
NOTE:Representative procedureThe described procedure is representative for Fischer Panda
generators. The original location of the item must be taken
from the generator description of this manual. All
replacements and repairs should be done by a trained
person.
Fig. 7.21-1: Flame glow plug01. Flame glow plug
Symptoms indicating a faulty start-up aid:
• Hesitant start-up
• Black exhaust smoke
• Irregular operation
• Increased fuel consumption, engine is „knocking“.
Electrical test
1. Check cable connections.
2. Check power consumption: approx. 8A.
3. Uninstall and check intake port for diesel residue. Replace flame glow plug if necessary.
Fig. 7.21-2: Flame glow plug