One Jumper Reference Method
This method is used when the link includes:
• the loss of one connection at the near end cross connect
• the loss of one connection at the far end cross connect/outlet
• the loss of the cable plant
TIA/EIA -568-B, ISO 11801, and IEEE 802.3 (100 Base-X, 1000Base-X)
specify the one jumper method.
Note
This method is called ‘Method B’ in TIA-526-14A and ’Method A.1’
in TIA-526-7.
1. Connect one end of a black launch cable to the TX (transmit) port of
the fiber adapter that is attached to OMNISCANNER.
2. Connect the other end of that black launch cable to the RX (receive)
port of the fiber adapter that is attached to OMNIREMOTE.
3. Leave the two white fiber connectors dangling and unconnected.
4. Connect one end of another black launch cable to the TX (transmit)
port of the fiber adapter that is attached to OMNIREMOTE.
5. Connect the other end of that black launch cable to the RX (receive)
port of the fiber adapter that is attached to OMNISCANNER.
6. Leave the two white fiber connectors dangling and unconnected.
7. Press (Setup) to open the SETUP screen and then select Set
Reference to set the reference.
8. Disconnect only the following two ends: OMNIFIBER Main RX (receive)
and OMNIFIBER Remote RX (receive). OMNIFIBER Main TX and OMNIFIBER
remote TX stay connected!
9. Connect the white fibers to the appropriate RX ports.
2 m Launch Cables