3 - 3
OMNISCANNER User Guide
Scanlink Tools support the following:
• Upload test results
• Storage of test results to files (Scanlink proprietary format)
• Print test reports
• Export results in CSV format
• Setup Projects
• Edit Autotest Information
Setting the Reference for Fiber Optic Cabling
Note
To ensure consistent accurate measurements,
the reference value must be set each time the
connector adapter or the test configuration is
changed. Since the reference value expires
each day at midnight, a reference must be
established least once each calendar day that
the OMNIFIBER is used.
1. Attach the connector adapters to each of the
OMNIFIBER RX ports.
2. To set the reference value, connect the
OMNIFIBER MAIN and OMNIFIBER REMOTE using
launch cables (jumpers) and couplers. See
Chapter 8 - Fiber Optic Reference Methods for
further information.
3. Press (Setup) and then select Set
Reference.
4. The CONNECT JUMPERS screen will display
how the jumpers need to be connected so that
the reference value can be recorded.
5. Connect the jumpers as shown and press
(Continue) to collect the reference data
while the SET REFERENCE screen is displayed.
OMNISCANNER will store a separate reference value for each wavelength.