OMNISCANNER User Guide
3 - 6
4. Press .
1 JUMPER METHOD AUTOTEST
To run an Autotest when the 1-Jumper Method was used to set the
Reference proceed as follows:
1. Do not disconnect the black connectors which are attached to the TX
port of the OMNIFIBER.
2. Disconnect the black connectors that are attached to the RX ports of
the OMNIFIBER.
3. Connect the white connectors to the RX ports on the OMNIFIBER.
4. Connect the OMNIFIBER MAIN to one end of the duplex link under test
and the OMNIFIBER REMOTE to the opposite end.
5. Press .
3 JUMPER METHOD AUTOTEST
To run an Autotest when the 3-Jumper Method was used to set the
Reference proceed as follows:
1. Do not disconnect the launch cables that are attached to the
OMNIFIBER.
2 m Launch Cable
2 m Launch Cable
Patch Panel
Wall Plate
Cable under Test
2 m Launch Cable
2 m Launch Cable
Patch Panel
Wall Plate
Cable under Test