A - 5
OMNISCANNER User Guide
TABLE A1.2: CALCULATED TYPICAL ACCURACY PER TIA ERROR
MODEL AS A FUNCTION OF MEASUREMENT CONFIGURATION
Typical Accuracy @ 100 MHz Basic Link Permanent Channel
measuring a 50 m link/chan. (Baseline) Link
Insertion Loss Accuracy 0.6 dB 0.8 dB 1.0 dB
PP NEXT Accuracy 0.5 dB 0.8 dB 1.2 dB
PS NEXT Accuracy 0.5 dB 0.8 dB 1.2 dB
PP ELFEXT Accuracy 0.8 dB 1.1 dB 2.7 dB
PS ELFEXT Accuracy 0.8 dB 1.1 dB 3.0 dB
RL Loss Accuracy 0.5 dB 0.9 dB 0.8 dB
Wire Map
· Finds miswires, opens, shorts, crossed and split pairs and presents
results in a schematic format
· Includes shield test if connected
· Uses OMNIREMOTE for complete mapping of wiring at both ends of the
cable
NEXT
· Test all six pair combinations from both directions using OMNIREMOTE
· Frequency Range: 1 to 300 MHz
· Dynamic Range: >100dB
· Measurement Accuracy: Calculated per TIA error model
· Accuracy: Significantly exceeds Level III requirements
· Measurement Resolution: 0.1dB
Return Loss
· Measures Return Loss on all four pairs from both directions using
OMNIREMOTE
· Frequency Range: 1.0 to 300 MHz
· Dynamic Range: > -35 dB
· Factory Calibrated to ensure measurement port match to reference
100 ohm impedance.
· Measurement accuracy: Significantly exceeds Level III requirements
· Measurement resolution: 0.1dB
Attenuation
· Tests all four pairs using OMNIREMOTE as far end active signal injector.
· Frequency Range: 1.0 to 300 MHz
· Dynamic Range: > 60 dB