5.2 Function Code Tables
5-17
FUNCTION CODES
Chap 5
Function
code
Name
Control method and Data setting range
Change when running
Data copying
Factory
default
Related page
C41
Analog input adjustment
(Terminal [V2])
(offset)
Same as C31
Y*
Y
0.0
C42
(Gain)
Same as C32
Y*
Y
100.00
C43
(Filter)
Same as C33
Y
Y
0.05
C44
(Gain base point)
Same as C34
Y*
Y
100.00
C45
(polarity selection)
Same as C35
N
Y
1
C50
Bias (for frequency setting
1)
(Bias base point)
0.00 to 100.00 %
Y*
Y
0.00
5-199
C51
Bias (PID command 1)
(bias value)
-100.0 to 0.00 to 100.00%
Y*
Y
0.00
C52
(Bias base point)
0.00 to 100.00 %
Y*
Y
0.00
C53
Selection of normal/inverse
operation
(Frequency setting 1)
0: Normal 1: Inverse
Y
Y
0
5-199
C54
(Frequency setting 2)
Y
Y
0
C55
Analog input adjustment
(Terminal [12])
(Bias)
-200.0 to 0.00 to 200.00%
Y*
Y
0.00
5-196
C56
(Bias base point)
0.00 to 100.00 %
Y*
Y
0.00
C58
(Display unit)
Same as J105 (0 cannot be set.)
Y
Y
2
5-199
C59
(maximum scale)
-999.0 to 0.00 to 9990.0
N
Y
100.00
5-200
C60
(minimum scale)
-999.0 to 0.00 to 9990.0
N
Y
0.00
C61
Analog input adjustment
(Terminal [C1] (C1 function))
(Bias)
-200.0 to 0.00 to 200.00 %
Y*
Y
0.00
5-196
C62
(Bias base point)
0.00 to 100.00 %
Y*
Y
0.00
C64
(Display unit)
Same as J105 (0 cannot be set.)
Y
Y
2
5-199
C65
(maximum scale)
-999.0 to 0.00 to 9990.0
N
Y
100.00
5-200
C66
(minimum scale)
-999.0 to 0.00 to 9990.0
N
Y
0.00
C67
Analog input adjustment
(Terminal [V2])
(Bias)
-200.0 to 0.00 to 200.00 %
Y*
Y
0.00
5-196
C68
(Bias base point)
0.00 to 100.00 %
Y*
Y
0.00
C70
(Display unit)
Same as J105 (0 cannot be set.)
Y
Y
2
5-199
C71
(maximum scale)
-999.0 to 0.00 to 9990.0
N
Y
100.00
5-200
C72
(minimum scale)
-999.0 to 0.00 to 9990.0
N
Y
0.00
C74
Analog input adjustment
(Terminal [C1])
(V3 function) (Offset)
-5.0 to 5.0 %
Y*
Y
0.0
5-196
C75
(Gain)
0.00 to 400.00 %
Y*
Y
100.00
C76
(Filter)
0.00 to 5.00 s
Y
Y
0.05
C77
(Gain reference point)
0.00 to 100.00 %
Y*
Y
100.00
C78
(Operation selection)
0: Bipolar
1: Unipolar
N
Y
1
C82
(Bias)
-200.0 to 0.00 to 200.00 %
Y*
Y
0.00
5-196
C83
(Bias reference point)
0.00 to 100.00 %
Y*
Y
0.00
C84
(Display unit)
Same as J105 (0 cannot be set.)
Y
Y
2
5-199
C85
(Maximum scale)
The analog input monitor terminal [C1] (C1 and V2 functions) display in the -
999.0 to 0.00 to 9990.0 range can be converted into easily recognizable
physical quantities. This function can also be used for PID feedback and PID
command values.
N
Y
100.00
5-200
C86
(Minimum scale)
The analog input monitor terminal [C1] (C1 function) display in the -999.0 to
0.00 to 9990.0 range can be converted into easily recognizable physical
quantities. This function can also be used for PID feedback and PID
command values.
N
Y
0.00
C89
Frequency compensation 1
via communication
(Numerator)
-32768 to 32767
(Keypad display is 8000 to 7FFF (in hexadecimal))
(Interpreted as 1 when the value is set to 0)
Y
Y
1
5-200
C90
Frequency compensation 2
via communication
(Denominator)
Y
Y
1
C94
Jump frequency 4
0.0 to 599.0 Hz
Y
Y
0.0
5-190
C95
5
Y
Y
0.0
C96
6
Y
Y
0.0
C99
Digital setting frequency
0.00 to 599.00 Hz
Y*
Y
0.00
5-200