5.2 Function Code Tables
5-21
FUNCTION CODES
Chap 5
Function
code
Name
Control method and Data setting range
Change when running
Data copying
Factory
default
Related page
H30
Communication link
function
(Mode selection)
Frequency setting/torque command Run command
0: F01/C30 F02
1: RS-485 communication (Port 1) F02
2: F01/C30 RS-485 communication (Port 1)
3: RS-485 communication (Port 1) RS-485 communication (Port 1)
4: RS-485 communication (Port 2) F02
5: RS-485 communication (Port 2) RS-485 communication (Port 1)
6: F01/C30 RS-485 communication (Port 2)
7: RS-485 communication (Port 1) RS-485 communication (Port 2)
8: RS-485 communication (Port 2) RS-485 communication (Port 2)
Y
Y
0
5-228
H31
Link function
(Actual terminal operation
selection)
0: Disable
1: Enable
N
Y
0
5-228
H42
Capacitance of DC link bus
capacitor
For adjustment when carrying out replacement, 0 to 65535
Y
N
-
5-231
H43
Cumulative run time of
cooling fan
For adjustment when carrying out replacement, 0 to 99990 hours (updated in
10 hour units) Displays the cumulative run time for the cooling fan
Y
N
0
H44
Startup count for motor 1
For adjustment when carrying out replacement, 0 to 65535 times
Y
N
-
5-235
H45
Simulation failure
0: Disable
1: Occurrence of mock alarm
Y
N
0
5-235
H46
Starting mode
(Auto search delay time 2)
0.1 to 20.0 s
Y
Y1Y2
*6
5-235
H47
Initial capacitance of DC
link bus capacitor
For adjustment when carrying out replacement, 0 to 65535
Y
N
-
5-235
H48
Cumulative run time of
capacitors on printed circuit
boards
For adjustment when carrying out replacement, 0 to 99990 hours (updated in
10 hour units)
Change in cumulative motor run time (reset also possible)
Y
N
0
5-231
5-235
H49
Starting mode
(Auto search delay time 1)
0.0 to 10.0 s
Y
Y
0.0
5-236
H50
Non-linear V/f 1
(Frequency)
0.0 (Cancel), 0.1 to 599.0 Hz
N
Y
0.0
*11
5-236
H51
(Voltage)
0 to 240 V: AVR operation (200 V series)
0 to 500 V: AVR operation (400 V series)
N
Y2
0
*12
H52
Non-linear V/f 2
Same as H50
N
Y
0.0
H53
(Voltage)
Same as H51
N
Y2
0
H54
Acceleration time
(Jogging)
0.00 to 6000 s
Y
Y
*10
5-236
H55
Deceleration time
(Jogging)
Y
Y
*10
*2: Factory defaults are depended on motor capacity. Refer to Table 5.2-1 Factory default settings by inverter capacity.
*6: Factory defaults are depended on motor capacity.
*10: 6.00 s for FRN0115G2S-2G/FRN0060G2-4G or lower inverters, 20.00 s for FRN0146G2S-2G/FRN0075G2-4G or higher inverters
*11: If F37 = 0, 5.0 Hz is automatically set for FRN0146G2S-2G/FRN0075G2-4G or higher inverters.
*12: If F37 = 0, 20 V is automatically set for FRN0146G2S-2G/FRN0075G2-4G or higher 200V series inverters, and 40 V is set for 400V series
inverters.