5.3 Description of Function Codes 5.3.5 H codes (High performance functions)
5-213
FUNCTION CODES
Chap 5
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
H02, H03
Data initialization (Method, Target)
Related function codes: H193, H194 User preference dataset (Save, Protect)
Returns function code data to the factory default settings. The motor parameters are also initialized.
To change the H02/ H03 data, it is necessary to press the + / keys (simultaneous keying).
H03 data
Function
0
Disable initialization (Settings manually made by the user will be retained.)
1
Initialize all function codes (initialization in accordance with function code H02 setting)
2
Initialize motor 1 parameters in accordance with F42 (Drive control selection 1), P02
(Rated capacity) and P99 (Motor 1 selection)
3
Initialize motor 2 parameters in accordance with F42 (Drive control selection 2), A16
(Rated capacity) and A39 (Motor 2 selection)
4
Initialize motor 3 parameters in accordance with F42 (Drive control selection 1), b16
(Rated capacity) and b39 (Motor 1 selection)
5
Initialize motor 4 parameters in accordance with F42 (Drive control selection 2), r16
(Rated capacity) and r39 (Motor 2 selection)
11
Limited initialization (initialization other than communications function codes):
Communication can be continued after initialization.
12
Limited initialization (initialization of customizable logic function U codes only)
When all function codes are initialized, select the initialization method in advance with function code H02.
H02 selection
Initialization method when 1 is set to H03
Data=0
Fuji standard initial value
Initialize all function codes with the Fuji Electric standard factory
defaults.
Data=1
User preference dataset
Initialize the value with the user setting value saved by H194.
If the user preference dataset is not saved, initialize it with Fuji
standard initial value (H02=0).
For saving the user preference dataset, refer to items in function codes H193 and H194.
To initialize the motor parameters, set the related function codes as follows.
Step
Item
Content
Function code
Motor 1
Motor 2
Motor 3
Motor 4
(1)
Motor type
Selects the motor type.
P99
A39
b39
r39
(2)
Motor capacity
Sets the capacity (kW).
P02
A16
b16
r16
(3)
Data
initialization
Initialize motor
parameters
H03 = 2
H03 = 3
H03 = 4
H03 = 5
When initialization is complete, the function code H03 data returns to "0" (factory default setting).
If P02/A16/b16/r16 data is set to a value other than the standard nominal applied motor rating, data initialization
with H03 internally converts the specified value parameters values to the standard nominal applied motor rating.
(See Chapter 5 Table 5.2-2 Motor constants.)