5.3 Description of Function Codes 5.3.10 U codes (Customizable logic operation)
5-405
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
FUNCTION CODES
Chap 5
Configuration of function codes
If specifying function codes, set the code values (decimal values on left, hexadecimal values on right) in the following
table for function 1 (U04, etc.), and set the last two digits of the function code number for function 2 (U05, etc.)
Function codes that are not found in the following table cannot be specified. The data format that can be accessed
correctly is as follows. (However, values are restricted to the -9990 to 9990 range) [1], [2], [3], [4], [5], [6], [7], [8],
[9], [10], [12], [22], [24], [29], [35], [37], [45], [61], [67], [68], [74], [92], [93]
A data format other than the above cannot be accessed correctly, and should therefore not be used.
Group
Code
Group
Code
F
0
00
H
X
16
10
H
E
1
01
H
z
17
11
H
C
2
02
H
b
18
12
H
P
3
03
H
d
19
13
H
H
4
04
H
W1
22
16
H
A
5
05
H
X1
25
19
H
o
6
06
H
K
28
1C
H
M
8
08
H
H1
31
1F
H
r
10
0A
H
o1
37
25
H
U
11
0B
H
U1
39
27
H
J
13
0D
H
J1
48
30
H
y
14
0E
H
d1
54
36
H
W
15
0F
H
d2
55
37
H
Task process cycle setting (U100)
U100 data
Content
0
Automatically adjusts the task cycle from 1 ms to 20 ms depending on the number of
used steps. This is the factory default. It is recommended to use this value.
1
1 ms: Up to 10 steps. If it exceeds 10 steps, the customizable logic does not work.
2
2 ms: Up to 20 steps. If it exceeds 20 steps, the customizable logic does not work.
5
5 ms: Up to 50 steps. If it exceeds 50 steps, the customizable logic does not work.
10
10 ms: Up to 100 steps. If it exceeds 100 steps, the customizable logic does not work.
20
20 ms: 20 is set if 100 steps is exceeded.
127: Multi-task
Customizable logics are operated in parallel in 1 ms, 2 ms, 5 ms, 10 ms, and 20 ms
cycles depending on the step number range. Even if there are many steps overall, it is
possible to run specific customizable logics in short cycles.
The relationship between cycle and step number is as follows.
1 ms cycle task: Step 1 to 10
2 ms cycle task: Step 11 to 20
5 ms cycle task: Step 21 to 50
10 ms cycle task: Step 51 to 100
20 ms cycle task: Step 101 to 200
Step 201 to 260 cannot be used.
Note that if it exceeds the steps defined in 1, 2, 5 or 10, the customizable logic does not work.