5.3 Description of Function Codes 5.3.13 K codes (Keypad functions)
5-423
FUNCTION CODES
Chap 5
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
K16
K17
K20
K21
K22
Sub-monitor 1 display content
Sub-monitor 2 display content
Bar graph 1 display content
Bar graph 2 display content
Bar graph 3 display content
The displayed content can be selected from the following function codes based on the display type selected with
K15.
Refer to the description for function code E43, and "3.3.1 Operating Status Main Monitor and Sub-monitor" in
Chapter 3 of the multi-function keypad Instruction Manual (Detailed version) (INR-SI47-2422-JEC) for details of
the display content, and set in the following function codes.
Display location
Displayed content
Main monitor
E43 data
Sub-monitor 1
K16 data
Sub-monitor 2
K17 data
Bar graph 1
K20 data
Bar graph 2
K21 data
Bar graph 3
K22 data
K40
Reserved
Do not change.
K51
Traceback data overwrite selection
It is possible to set whether to allow or prohibit overwriting if the maximum number of data items that can be saved
is reached.
0: Allow (factory default), 1: Prohibit
Maximum number of data items that can be saved
When multi-function keypad TP-A2SW connected : max. 100 items (when microSD card inserted) (Note)
When standard keypad TP-E2 connected : up to 1 item
Note: Data cannot be saved when a microSD card has not been inserted.
K52
Traceback sampling cycle
Sets the analog input/output signal or digital input/output signal waveform sampling cycle when an event occurs.
There are 500 samples (fixed).
The following table shows the relationship between sampling cycle and the length of time that sampling is possible.
Sampling cycle
500[μs] (Setting value: 8)

200[ms] (Setting value: 7)
Sampling possible time
250[ms]

100[s]