Concord 4 Series Systems
41
The following sections describe the settings that appear under PARTITION 1-6.
Entry Delay (0310 - 0360)
Timers-Partition 1-6 (Default = 30 sec.)
This setting determines how much time the user has to disarm the system
(after entering the armed premises through a “designated delay door”)
without causing an alarm.
Note
For UL 1023 Listed installations, the Entry Delay must be set to 45 seconds or
less. The combined time for the Entry Delay and Dialer Abort Delay (02006)
must not exceed 60 seconds.
To set the Entry Delay:
1. With the display showing ENTRY DELAY nnn
SECS
(current setting), enter the desired time
value (30–240). The display flashes the
entered setting.
2. Press # and the display shows the new setting.
Exit Delay (0311 - 0361)
Timers-Partition 1-6 (Default = 60 sec.)
This setting determines how much time the user has (after arming the sys-
tem) to leave the premises through a “designated delay door” without
causing an alarm.
Note
For UL 1023 listed installations, this feature must be set to 60 seconds or less.
For UL 1610 listed installations, this feature must be set to 120 seconds or less.
To set the Exit Delay:
1. With the display showing EXIT DELAY nnn
SECS
(current setting), enter the desired time
value (45–184). The display flashes the
entered setting.
2. Press # and the display shows the new setting.
Extended Delay (0312 - 0362)
Timers-Partition 1-6 (Default = 4 min.)
This setting determines how much time the user has (after arming the sys-
tem) to enter or exit the premises through a “designated extended delay
door” (1–8 minutes).
Note
For UL Listed installations Extended Delay may not be used.
To set the Extended Delay:
1. With the display showing EXTENDED DELAY n
MINUTES
(current setting), enter the desired
time value (1–8). The display flashes the
entered setting.
2. Press # and the display shows the new setting.
Siren Timeout (0313 - 0363)
Timers-Partition 1-6 (Default = 4 min.)
This setting determines how long sirens sound (1–30 minutes) if
no one is present to disarm the system.
Note
For UL Listed installations, the Siren Timeout must be set to 4 min-
utes or more.
To set the Siren Timeout:
1. With the display showing SIREN TIMEOUT nn MINUTES
(current setting), enter the desired time value (1–30).
The display flashes the entered setting.
2. Press # and the display show the new setting.
Sleep Time (0314 - 0364)
Timers-Partition 1-6 (Default = 22:00 [10:00 pm])
This setting determines the start time and restart of a 10-hour window
during which trouble beeps are suppressed. The initial occurrence of
an event that causes trouble beeps within this window will not sound
trouble beeps until the Sleep Time window expires. If trouble beeps
from a previous event are due to be restarted during the sleep time
window, they will be restarted one hour prior to Sleep Time.
Note
For UL listed installations, this feature must be set to off.
To set the Sleep Time:
1. With the display showing SLEEP TIME hh:mm (cur-
rent setting), enter the desired time value (00:00-
23:50 using 10 minute intervals). The display
flashes the entered setting.
2. Press # and the display show the new setting.
To turn off Sleep Time:
1. With the display showing SLEEP TIME hh:mm (cur-
rent setting), press D.
WWW.DIYALARMFORUM.COM

Table of Contents

Other manuals for GE Concord 4 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Concord 4 Series and is the answer not in the manual?

GE Concord 4 Series Specifications

General IconGeneral
User Codes230
Backup Battery12V 4Ah rechargeable battery
Wireless Frequency319.5 MHz
CommunicationPOTS, optional cellular and IP modules
Wireless CapabilityYes
Keypad OptionsMultiple keypad options including touchscreen
Wired Zones8 on board
Power Supply16.5 VAC Transformer
CompatibilityCompatible with GE Security wireless sensors
ZonesUp to 96
Event Buffer512