Chapter 5 Detailed Descriptions of I/O Modules
GFK-2958E RSTi-EP User Manual 259
Specifications EP-3468
Process, parameter and diagnostic data depend on the
network adapter used (refer to the table in the section, Order
and Arrangement of the Modules)
RSTi-EP I/O communication bus
Current input (0 - 20 mA, 4 - 20 mA)
max. 0.1 % FSR
±50 ppm/K max.
at 25 °C (77 °F)
Temperature coefficient
max. 125 mA per channel; channel 0 - 3 and 4 - 7 respectively
are fused in combination
2-wire, 3-wire, 3-wire + FE
Reverse polarity protection
Response time of the protective circuit
< 0.1 s with short-circuit to +24 V
Temperature-dependent: < 30 s at 20°C (-4 °F)
Individual channel diagnosis
Current consumption from system current path I
SYS
,
Current consumption from input current path I
IN
Insulation Displacement Connection (IDC)
Line connection cross-section
0.14 - 0.35 mm
2
(26 – 22 guage)
For additional general data, refer to the section General Technical Data for I/O Modules.