Chapter 5 Detailed Descriptions of I/O Modules
GFK-2958E RSTi-EP User Manual 260
Overview of the Editable Parameter EP-3468
Channel
Description
Options
Default
Frequency suppression
disabled (0) / 50 Hz (1) / 60 Hz (2) / Average over 16 values (3)
disabled
0 - 7
Channel diagnostics
disabled (0) / enabled (1)
disabled
0 - 7
Diag short circuit 24 V
disabled (0) / enabled (1)
Disabled
0 - 7
Measurement range
0 to 20 mA (0) / 4 to 20 mA (1) / disabled (3)
disabled
Process Data
Inputs EP-3468
Byte
Format
Description
Remarks
IB0
Word
AI0
IB1
IB2
Word
AI1
IB3
IB4
Word
AI2
IB5
IB6
Word
AI3
IB7
IB8
Word
AI4
IB9
IB10
Word
AI5
IB11
IB12
Word
AI6
IB13
IB14
Word
AI7
IB15
Internal process data mapping with data format Standard. Depending on the fieldbus specification and the data
format of the communicating fieldbus components the bytes and/or words can be reversed during data transfer.