EasyManua.ls Logo

GE RSTi-EP - Page 41

GE RSTi-EP
425 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 3: Configuration
GFK-2958E RSTi-EP User Manual 37
Module behavior on hot swap
Continue data
exchange / Behavior
like fieldbus error
Continue data
exchange
Data format
Motorola / Intel
Motorola
Webserver via Ethernet
enabled / disabled
disabled
Product
Part No.
Parameter
Optional values
Default value
Ethercat Network
Adapter, 2 Cu RJ45
Ports, 1024 bytes
(Input + Output)
EPXETC001
Process alarm
enabled / disabled
disabled
Diagnostic alarm
enabled / disabled
disabled
Behavior of outputs on fieldbus
errors
All outputs off /
Enable substitute
value / Hold
last value
All outputs off
Module behavior on hot swap
Continue data
exchange / Behavior
like fieldbus error
Continue data
exchange
Data format
Motorola / Intel
Intel
Webserver via Ethernet
enabled / disabled
enabled
Network adapter control
Reserved
Off
Product
Part No.
Parameter
Optional values
Default value
Modbus TCP Network
Adapter, 2 Cu RJ45
Ports, 2048 bytes
(Input + Output)
EPXMBE001
/EPXMBE101
IP-Address
#
# In Dual LAN Mode
(EPXMBE101 only)
parameterizable for each
Ethernet Port
4 numbers between
0-255
192.168.0.222
Subnet mask
#
# In Dual LAN Mode
(EPXMBE101 only)
parameterizable for each
Ethernet Port
4 numbers between
0-255
255.255.255.0
Gateway#
# In Dual LAN Mode
(EPXMBE101 only)
parameterizable for each
Ethernet Port
4 numbers between
0-255
192.168.0.1
IP Configuration
#
# In Dual LAN Mode
(EPXMBE101 only)
parameterizable for each
Ethernet Port
Static, DHCP, BootP
Firmware 02.00.00
and higher:
additionally DHCP
and static
Static (firmware
01.xx.xx)
DHCP and static
(firmware
02.00.00 or higher)
Modbus Dual LAN Mode
(EPXMBE101 only)
disabled / enabled
disabled
Modbus DHCP Timeout
Waiting time, 1 to
1000 s
30 s
IP-Address USB-Port
192.168.1.202;
192.168.2.202,
192.168.3.202,
192.168.4.202,
192.168.5.202
192.168.1.202
Webserver via Ethernet
disabled / enabled
enabled

Table of Contents

Other manuals for GE RSTi-EP

Related product manuals