Chapter 3: Configuration
GFK-2958E RSTi-EP User Manual 38
Save module parameters
no / yes / Standard
no, see register
0x113C-0x113F
Status Modbus watchdog
Watchdog time in
steps of 10 ms
0 *10 ms, see
register 0x1120
Modbus Connection Timeout
Connection
watchdog time in sec
1 s, see register
0x1131
Writing access with multiclient
write for all,
1stWr1stServe,
1stConn1stServe
write for all, see
register
0x1130
Check reference list before
exchanging data
disabled / enabled
disabled, see
register 0x1132
Process alarm
disabled / enabled
disabled ,see
register 0x1133
Diagnostic alarm
disabled / enabled
disabled ,see
register 0x1134
Behavior of outputs on fieldbus
error
All outputs off /
Enable substitute
values / Hold
last value
All outputs off, see
register
0x1135
Module behavior on hot swap
Continue data
exchange / Behavior
like fieldbus
error
Continue data
exchange,
see register
0x1136
Data format
Motorola / Intel
Motorola, see
fieldbus register
0x1137
Product
Part No.
Parameter
Optional values
Default value
Digital Input, 4 Points,
Positive Logic 24VDC,
2, 3, or 4 Wire
EP-1214
Ch 0 … Ch 3: Input delay
no (0)/0,3 ms (1) (not
at PROFIBUS-
DP)/3ms
(2)/10 ms (3)/20 ms
(4)/40 ms (5) (not at
PROFIBUS-DP)
3 ms
Product
Part No.
Parameter
Optional values
Default value
Digital Input, 8 Points,
Positive Logic, 24VDC
2 Wire
Digital Input, 8 Points,
Positive Logic, 24VDC
3 Wire
EP-1218
EP-1318
Ch 0 … Ch 7: Input delay
no (0) / 0,3 ms (1) (not
at PROFIBUS-DP) / 3
ms
(2) / 10 ms (3) / 20 ms
(4) / 40 ms (5) (not at
PROFIBUS-DP)
3 ms
Product
Part No.
Parameter
Optional values
Default value
Digital Input, 4 Points,
Positive Logic 24VDC,
2, 3, or 4 Wire, Time
stamp
EP-12F4
Ch 0 … Ch 3: Input delay
no (0) / 0,3 ms (1) (not
at PROFIBUS-DP) /3
ms
(2) / 10 ms (3) / 20 ms
(4) /40 ms (5) (not at
PROFIBUS-DP)
3 ms
Ch 0 … Ch 3: TimeStamp at
edge 0-1
disabled (0) /
enabled (1)
disabled