Table 2-105 CLI console operation
Item Operation
Displaying APC setting show power setting
Setting APC values set power capping
The following example shows the power management flow when the
Maximum power consumption is set to 2000W.
The system specifications for the example are as follows:
•
APC maximum for the system unit: 2000 W
• Power consumption for modules other than server blades: 800 W
The maximum power consumption for server blades: 1200 W
• Power consumption specification for server blades:
Rating power consumption (Maximum): 400 W
Maximum power consumption when capping to the minimum value: 150
W
• Number of server blades installed: 4 with the same power consumption
specifications
• APC: Enable
When the total power consumption of the chassis exceeds the APC
maximum, power consumption of four sever blades will be limited to 300
W respectively.
1. Operation status 1 (Operating within the maximum power consumption)
2. Operation status 2 (Exceeding the maximum power consumption)
Functional detail
2-219
Hitachi Compute Blade 500 Series Management Module Setup Guide