Miscellaneous
AC FAIL and Panel Tamper Inputs
The panel has the following two additional generic inputs that can be used as generic
inputs or as either External Power Fail or Enclosure Tamper inputs. The default condition
is a two-state input configured as Normally Closed. Input 14 is a special case, since it
reports in as two inputs (inputs 14 and 20). Input 14 can be used as a generic input, but
input 20 is used for the Enclosure Tamper alarm. An active External Power Fail input
indicates that the system is operating from the battery current, not from the primary input
power. An inactive External Power Fail input indicates that the system is operating from
the primary input power. About the resistor connection of TB8 supervisors, please see
Figure 3-7 Typical Supervised Input Wiring Diagram.
Table A-5 Default AC FAIL and Panel Tamper Inputs
Generic input Panel input Reports as...
Generic/External Power Fail SUP5 Input 5
Generic/Enclosure Tamper SUP6 Input 6
Additional Generic Outputs
The panel has the following two additional generic form C relay outputs:
Table A-6 Additional Generic Outputs
Relay output Controls...
3 Output 3
4 Output 4