Table 816: Log-off Request Components
Component Description
<$4B> Command request identifier. See Table 814.
<Receiver ID> Receiver ID number. 1 or 2 ASCII digits.
<$22> Separator
<User PIN> The users PIN code.
<V-byte> Validation Byte (V-byte). See 8.4.5.
<$0D> End of message indicator.
8.4.7.2 Force Hang-up Request
This command is used to immediately hang up the phone line regardless of the state of the line card.
To Force Hang-up:
<$05><Receiver ID><$22><LC#><V-byte><$0D>
Table 817: Force Hang-Up Request Components
Component Description
<$05> Command request identifier. See Table 814.
<Receiver ID> Receiver ID number. 1 or 2 ASCII digits.
<$22> Separator
<LC#> The LinePort number.
<V-byte> Validation Byte (V-byte). See 8.4.5.
<$0D> End of message indicator.
8.4.7.3 Add or Delete a Listen-in Account
If the account number of a control panel is in the listen-in account list, when that control panel calls in to the
receiver, the receiver will perform a listen-in operation with that control panel. The maximum length of a
listen-in account number is 8 characters and may include wild card characters (# and or *). Each line card
can have up to 20 listen-in account strings. See also Section 5.5.2.4.
Note: The listen-in account list applies to panels that do not send listen-in commands as a part of their
message (Contact ID E606 or SIA LF and LE).
To Add a Listen-in Account:
<$04><Receiver ID><$22><LC#><$22><Act#><V-byte><$0D>
Table 818: Add Listen-in Account Request Components
Component Description
<$04> Command request identifier. See Table 814.
<Receiver ID> Receiver ID number. 1 or 2 ASCII digits.
<$22> Separator
<LC#> The LinePort number.
<$22> Separator
<Act#> Account number to be added to the listen-in account list.
<V-byte> Validation Byte (V-byte). See 8.4.5.
<$0D> End of message indicator.
To Delete a Listen-in Account:
<$03><Receiver ID><$22><LC#><$22><Act#><V-byte><$0D>
Table 819: Delete a Listen-in Account Request Components
Component Description
<$03> Command request identifier. See Table 814.
<Receiver ID> Receiver ID number. 1 or 2 ASCII digits.
<$22> Separator
<LC#> The LinePort number.
<$22> Separator
<Act#> Account number to be deleted from the listen-in account list.
<V-byte> Validation Byte (V-byte). See 8.4.5.
<$0D> End of message indicator.